Cable glands for industrial and hazardous-area cable in Saudi Arabia

Industrial and Ex cable glands for unarmored, wire-armored and braided cable: Ex d compression and barrier glands, Ex e and dual-certified types, plus shrouds, earth tags, locknuts, sealing washers, adaptors and stopping plugs. JTE supplies them from established manufacturers, with the maker’s IECEx or ATEX certificate.

A cable gland is the fitting that brings a cable into an enclosure, seals it, holds it and keeps the enclosure’s protection intact. On armored cable it also clamps the armor and earths it. Industrial cable glands for ordinary areas are covered by IEC 62444 (EN 62444, which replaced EN 50262). Glands for explosive atmospheres are certified to the IEC 60079 series and installed to IEC 60079-14. The right gland depends on cable construction, outer diameter, enclosure protection type, zone, gas group, entry thread and site environment.

Non-Ex standard
IEC 62444 / EN 62444 (replaced EN 50262); BS 6121-1 still cited by makers
Ex standards
IEC 60079-0 general, -1 flameproof d, -7 increased safety e, -15 type n (nR), -31 dust t
Installation
IEC 60079-14, edition 6 (2024) for Ex selection and erection
Cable types
Unarmored, SWA, AWA, wire braid, steel tape, pliable wire, lead sheathed
Protection
Ex db, Ex eb, Ex nR, Ex ta/tb; dual and multi-certified types
Ingress
IP66 typical; IP67 and IP68 on many glands; deluge seals available
Materials
Brass, nickel-plated brass, 316 stainless steel, aluminum, nylon
Threads
Metric ISO (M16 to M130), NPT, PG on older equipment
Bundled industrial power cables
Bundled industrial power cables (photo for illustration)

What we supply

Industrial glands
Brass, stainless and nylon glands for unarmored and armored cable in safe areas
Ex d and Ex e glands
Certified compression glands for Zone 1 and Zone 2 equipment
Barrier glands
Compound-filled Ex d glands with the maker’s compound kit
Dual-certified glands
Ex d / Ex e / Ex nR glands for mixed equipment schedules
Accessories
Shrouds, earth tags, locknuts, sealing and serrated washers, adaptors, reducers, stopping plugs
Gland kits
Glands and accessories packed and labeled per cable schedule line

Cable gland types and where each one fits

Gland type follows the cable construction first and the protection concept second. The table groups the common types used in Saudi process plants and utilities.

Common cable gland types by cable and protection concept
Gland typeCable it suitsHow it seals and clampsTypical use
Industrial gland, unarmoredPVC, LSZH or rubber sheathed cableSingle seal on the outer sheath; clamp by seal or clawSafe-area panels, motors, lighting
Industrial gland, armoredSWA, AWA, braid or tape armoredArmor clamp with outer seal; inner seal on some typesSafe-area power and control cable
Ex e glandUnarmored or armored cableOuter seal (and inner seal on armored types)Increased-safety junction boxes, Ex e motors
Ex d compression glandCable meeting IEC 60079-14 cable criteriaElastomeric flameproof seal on the inner sheath or cableFlameproof enclosures where a barrier is not required
Ex d barrier glandAny cable, including those with fillers and voidsTwo-part compound set around each coreFlameproof enclosures where the selection rules call for a barrier
Dual or multi-certifiedArmored or unarmored, per certificateEx d seal plus Ex e and Ex nR approvals on one glandPlants that stock one gland family for many enclosures
Ex nR glandCable that keeps the restricted-breathing sealInner seal air-tight in both directionsRestricted-breathing Zone 2 enclosures

Each gland is used only within its certificate. Check the protection concepts, gas group, EPL, temperature range and any conditions of use on the maker’s IECEx or ATEX certificate.

Oil and gas supplyPetrochemical supply

Typical gland sizes by cable outer diameter

Gland size is chosen from the cable’s measured outer diameter, not from the conductor size. The ranges below come from one maker’s published table for an Ex d / Ex e armored gland; other makers use different size codes and ranges.

Example size ranges, armored Ex gland (overall cable diameter, mm)
Gland sizeMetric entry threadOuter sheath min (mm)Outer sheath max (mm)
20S16M206.113.1
20SM209.515.9
20M2012.520.9
25SM2514.022.0
25M2518.226.2
32M3223.733.9
40M4027.940.4
50SM5035.246.7
50M5040.453.0
63SM6345.659.4
63M6354.665.8
75SM7559.072.0
75M7566.778.4
90M9076.290.3

Typical values only. Inner sheath (bedding) range and armor thickness range must also fit, and they vary by maker. Send the cable datasheet or the measured diameters with your enquiry.

Cable glands in Saudi refineries, petrochemical plants and utilities

Plants in Jubail Industrial City, Ras Tanura and Ras Al Khair combine Zone 1 and Zone 2 areas with a hot, salty, dusty coastal climate. The points below are what usually decides the gland on these sites. Your project specification and area classification drawings remain the final word.

What Saudi plant conditions mean for cable gland selection
RequirementWhat it means
Area classificationZone 1 needs EPL Gb glands (Ex db or Ex eb); Zone 2 accepts Gc or better. Read the zone and gas group from the hazardous-area drawing, not from habit.
Gas groupHydrogen service in refineries and some petrochemical units needs IIC. A IIC gland can be used in IIA and IIB areas, not the reverse.
Certification schemeProjects usually ask for an IECEx certificate, ATEX, or both. The gland carries the manufacturer’s certificate; the supplier passes on a copy.
Barrier decisionMany owner specifications set their own barrier rule, often stricter than IEC 60079-14. Follow the project rule where it is stricter.
Salt and humidityCoastal sites favor nickel-plated brass or 316 stainless steel. Plain brass tarnishes and aluminum needs care with copper-bearing armor.
Sand and dustUse IP6X dust-tight glands and entry thread sealing washers. Shrouds keep sand out of the armor clamp area.
Sun and heatCheck the seal’s rated temperature range against the enclosure surface in direct sun. Use UV-stable shrouds outdoors.
Deluge and washdownOffshore and fire-water deluge areas may call for deluge-tested glands with an extra outer seal.
DocumentsCertificate copies, the maker’s installation instructions and the gland schedule should travel with the material for site inspection.

No Saudi Aramco or SABIC document is cited here because we could not verify the current revision on a public source. Check your project specification for owner-specific gland, barrier and material rules.

Where cable glands are used

Every cable that enters a panel, junction box, motor terminal box or instrument housing needs a gland suited to that entry.

Motors and pumps

Ex e and Ex d motor terminal boxes on pumps, compressors and fans in process units.

Junction boxes

Ex e power and control junction boxes, where glands must keep the box at IP54 or better.

Instruments

Transmitters, analyzers and solenoid valves, often with M20 or 1/2 in. NPT entries.

Lighting and stations

Flameproof light fittings, control stations and plugs and sockets in Zone 1 and Zone 2.

Substations and MCCs

Brass or aluminum armored-cable glands into switchgear and gland plates in safe areas.

Coastal and offshore

Nickel-plated brass and 316 stainless glands for jetties, desalination and marine plant.

Glands matched to your cable schedule

Send the cable schedule and we match each line to a gland size, seal type, thread and material from certified ranges.

  • Sized from cable outer diameter
  • Armor type checked
  • Thread and entry checked
  • Accessories per line
  • Kits labeled by tag

Our services

Documents with the order

Hazardous-area glands are only as good as their paperwork at site inspection.

  • Maker’s IECEx or ATEX certificate copy
  • Installation instructions
  • Packing list by cable tag
  • Third-party inspection on request
  • ISO 9001 supplier

Quality and documents

What a cable gland does

A cable gland has four jobs: seal, retain, earth and protect. It seals the cable to the enclosure so water and dust stay out. It grips the cable so pulling or vibration does not strain the terminals.

On armored cable the gland also clamps the armor or braid and carries fault current to earth. In a hazardous area it must keep the enclosure’s type of protection intact, so a flameproof box stays flameproof after the cable goes in.

A gland is not a generic fitting. It is sized to one cable diameter range, one entry thread and one set of approvals. Choosing it is part of the electrical design, not a site purchase.

Parts of a typical armored gland

Most armored glands share the same parts, although names differ between makers.

  • Entry component: the threaded body that screws into the enclosure.
  • Inner seal: seals on the inner sheath (bedding) of armored cable; in Ex d glands this is the flameproof seal.
  • Armor clamp: a cone and clamping ring that grip SWA, AWA, braid or tape and provide the earth path.
  • Outer seal: seals on the outer sheath to keep water off the armor.
  • Back nut and middle nut: tighten the seals and the armor clamp.
  • Accessories: shroud, earth tag, locknut and sealing washer at the entry.

Gland types by cable construction

Start with the cable. The gland must suit the armor type and the sheath layers, or it will not clamp or seal correctly.

Unarmored cable needs only a seal and a retention grip. Armored cable needs an armor clamp as well, and usually a seal on both the inner and outer sheath.

Many makers and specifications still use the cable and gland letter codes that came from the British standard BS 6121. The codes below appear in a widely used IECEx gland selection guide.

Single and double compression glands

In Gulf and Indian purchasing, “single compression” usually means a gland that seals on one sheath. “Double compression” usually means sealing on both the inner and outer sheath with an armor clamp between them, close to an E-type gland.

These are trade terms, not standard names, and makers use them differently. On an RFQ, describe the seals and the armor clamp you need, not only the trade name.

Lead-sheathed and screened cable

Some refinery cable has a lead sheath under the armor for chemical resistance. Glands for it add an electrical bond to the lead sheath, for example the E2W style. Braided screened (EMC) cable needs a clamp that bonds the braid all round.

Cable armor codes and gland sealing codes used in gland names
CodeMeaningNotes
WSingle wire armor (SWA) or aluminum wire armor (AWA)The most common armored power cable
XWire braidCommon on instrument and flexible cable
TPliable wire armorFine wires; needs a clamp suited to thin armor
YAluminum strip armorLess common
ZDouble steel tape armorOlder and some imported cable
ASingle seal onlyUnarmored cable
BArmor clamp onlyNo seal; dry indoor use
CArmor clamp with outer sheath sealCommon industrial armored gland
DArmor clamp with inner sheath sealSeal on bedding only
EArmor clamp with inner and outer sealsUsual choice for hazardous areas and outdoors

Ex d, Ex e, Ex nR and dual-certified cable glands

Hazardous-area glands are certified to the same protection concepts as the equipment they enter. The gland must meet or exceed the protection of that equipment.

Ex d (flameproof) glands are certified to IEC 60079-1. Their inner seal must be flameproof and gas-tight, and the entry thread must keep a flameproof joint with the enclosure. Makers state a minimum engagement of five full threads or 8 mm.

Ex e (increased safety) glands follow IEC 60079-7 and the general rules of IEC 60079-0. Their job is to keep the Ex e enclosure at IP54 or better and to resist impact and cable pull. One maker lists 7 J impact for Group II glands.

Ex nR glands serve restricted-breathing enclosures under IEC 60079-15. The cable and gland together must keep the enclosure’s restricted-breathing seal, and the inner seal must be air-tight both ways.

Dual and multi-certified glands

Many armored Ex glands carry several approvals at once, for example Ex db, Ex eb, Ex nR and Ex ta on one certificate. One such gland family is marked Ex db IIC Gb, Ex eb IIC Gb, Ex nR IIC Gc and Ex ta IIIC Da.

Plants like them because one gland family can serve flameproof, increased-safety and restricted-breathing boxes. Check that every approval you rely on is on the certificate for that exact gland type and size.

Dust protection

Where combustible dust is present, glands may also carry Ex t approval to IEC 60079-31. Examples are Ex ta IIIC Da and Ex tb IIIC Db. This matters for sulfur handling, grain and some polymer powder areas.

Current editions

IEC published edition 8 of IEC 60079-0 in June 2026 and edition 8 of IEC 60079-1 in October 2026. IEC 60079-7 is the 2015 edition with its 2017 amendment, and IEC 60079-15 is the 2017 edition. Gland certificates name the editions they were assessed to.

Which gland protection suits which equipment (based on the IEC 60079-14 compatibility table)
Equipment protectionEx d glandEx e glandEx nR gland
Ex d (flameproof)YesNoNo
Ex e (increased safety)YesYesNo
Ex nR (restricted breathing)Yes, if it keeps the nR sealYes, if it keeps the nR sealYes
Ex i (intrinsic safety), Group IIYesYesYes
Ex p (pressurized)YesYesYes

How to read IECEx and ATEX gland marking

Ex marking tells you where the gland may be used. Read it from left to right and match each part to the area and the equipment.

IECEx marking starts with the protection concept, gas group and EPL, such as Ex db IIC Gb. ATEX marking adds the hexagon Ex symbol and the equipment group and category, such as II 2 G. It also carries a CE mark with the notified body number.

Cable glands do not normally carry a temperature class (T rating) of their own. They carry a service temperature range for the seal and body. The temperature class of the installation comes from the equipment the gland enters.

  • Zone 1 needs EPL Gb or Ga equipment; Zone 2 accepts Gc, Gb or Ga.
  • IIC glands can go into IIB and IIA areas; IIA glands cannot go into IIB or IIC areas.
  • An IECEx certificate can be checked on the public IECEx online register by its number.
Example: II 2 G Ex db IIC Gb, broken down
PartMeaningWhat to check
IIEquipment group II: surface industries (Group I is mining)Group II for refineries and chemical plants
2 GATEX category 2, gasCategory 2 suits Zone 1; category 3 suits Zone 2 only
Ex dbFlameproof, level of protection bMatches a flameproof enclosure
IICGas group IIC (hydrogen, acetylene)IIC also covers IIB and IIA
GbEquipment protection level Gb (high)Gb for Zone 1; Gc for Zone 2 only
X after the certificate numberSpecific conditions of use applyRead the conditions on the certificate before installing
Service temperatureFor example -60 °C to +130 °C on one maker’s glandRange varies by seal material and maker

When a barrier gland is needed

A barrier gland seals around each conductor with a two-part compound, so gas and flame cannot travel through the cable core. A compression gland seals only on the cable sheath.

IEC 60079-14 sets the selection rule, and it has changed between editions. Edition 5 (2013) replaced the older selection chart with conditions. One was a 3 m minimum cable length to avoid a barrier gland in many cases. The UK HSE and EEMUA raised safety concerns about that change.

Edition 6, published in August 2024, brings back a flowchart for Ex d cable entry devices. It considers gas group, hydrogen, cable length and enclosure volume, and adds a normative Annex C pressure test for cables.

The 2024 selection logic in outline

The summary below follows published guidance on edition 6. Always apply the full text of the standard and your project specification.

  • Minimum connected cable length: 3 m for IIC and hydrogen applications; 0.5 m for other gas groups.
  • If the cable is shorter than that minimum, use a flameproof entry device with a barrier around the conductors.
  • For IIA and IIB with the length met, an elastomeric-seal gland is allowed into an enclosure of 2000 cm³ or less.
  • Above 2000 cm³, or if the volume is not known, the cable must be assessed to Annex C; without that evidence, use a barrier gland.
  • Cable and entry device are considered together for direct entry into flameproof and restricted-breathing enclosures.

Practical rule on site

Many owners and contractors simply specify barrier glands for all direct entries into Ex d enclosures. It costs more in time, but it removes argument at inspection. A widely used selection guide gives the same advice: if in doubt, use a barrier gland.

Barrier compound comes as a moldable putty or a pourable resin. Either way, the cable must not be moved while the compound cures, and the maker’s cure time must pass before energizing.

Ingress protection, deluge and impact

IP ratings follow IEC 60529. The first digit is dust and the second is water. IP6X means dust-tight, which is the right target for desert sites.

IP66 means protection against powerful water jets: about 100 liters per minute from a 12.5 mm nozzle at 2.5 to 3 m for at least 3 minutes. IP67 means temporary immersion to 1 m for 30 minutes. IP68 means continuous immersion on terms agreed with the maker, so always read the stated depth and time.

IP66 and IP67 are separate tests. A gland marked IP66 only has not been proven for immersion. Some Ex glands are marked IP66 and IP68 together, for example IP68 at 30 m for 7 days on one maker’s barrier gland.

  • Ex e enclosures need IP54 minimum under IEC 60079-7; the gland must not lower the box rating.
  • The IP rating of the joint usually depends on an entry thread sealing washer or O-ring. Use the one tested with the gland.
  • Deluge-tested glands (to the DTS01 test, offered by some makers) add an outer seal for fire-water deluge zones.
  • One maker quotes IK10 (20 J, IEC 62262) impact resistance for its brass and stainless glands.

Gland materials and corrosion

Brass is the default gland body. It machines well, carries earth fault current and suits most indoor and sheltered locations.

Nickel-plated brass is the usual choice for coastal process plants. One gland selection guide advises specifying at least 10 microns of electroless nickel. 316 stainless steel is used where salt spray, splash or chemical vapor is severe, and on offshore and jetty work.

Aluminum glands suit aluminum enclosures and aluminum wire armor, avoiding a dissimilar-metal joint. Nylon (polyamide) glands are used on unarmored cable in safe areas, and some plastic glands carry Ex approvals; check the certificate.

Seals and dissimilar metals

Seal compounds differ between makers: neoprene, silicone and halogen-free thermoset elastomers are common. Low-smoke, halogen-free seals are often asked for in enclosed plant rooms.

Match the gland material to the enclosure and armor where you can. Where metals differ, use the maker’s recommended washers and keep the joint dry with shrouds.

Choosing a gland material
MaterialStrengthsWatch forTypical location
BrassStrong, conductive, economicalTarnishes in salt air; avoid ammonia-rich atmospheresIndoor MCCs, sheltered plant
Nickel-plated brassBetter corrosion resistance than plain brassSpecify plating thickness; damaged plating corrodesOutdoor process units on the coast
316 stainless steelBest general corrosion resistanceHigher cost; check galling on threadsOffshore, jetties, desalination, chemical splash
AluminumLight, matches aluminum enclosures and AWAGalvanic attack with copper and brassAluminum Ex enclosures
Nylon (polyamide)Light, no corrosion, low costUV and heat aging; no armor earth pathUnarmored cable in safe areas

Entry threads, sizes and adaptors

The gland thread must match the entry on the equipment exactly. Most IEC equipment uses metric ISO threads with a 1.5 mm pitch; North American and some instrument equipment uses NPT tapered threads.

PG threads are an older German system. They still appear on some older equipment, but metric threads have largely replaced them. Do not mix PG and metric: they look close but are not interchangeable.

Metric Ex gland thread length is typically 15 mm for sizes up to M75, and longer on large sizes. Ex d entries need enough engagement to keep the flamepath; makers quote five full threads or 8 mm minimum.

  • Equivalents are approximate. Never force a gland into a thread it was not made for.

Adaptors, reducers and stopping plugs

When the gland fits the cable but the thread does not fit the entry, a thread adaptor or reducer solves it. In a hazardous area the adaptor must be Ex certified for the same protection concept, and many certificates limit how adaptors may be stacked.

Unused entries must be closed with a certified stopping plug (blanking element) of the right protection type. A plastic transit cap from the factory is not a stopping plug.

Common entry threads, approximate equivalents
Metric (EN 60423)PitchOlder PG size (outside dia.)Nearest NPT
M16 x 1.51.5 mmPG 9 (15.2 mm)3/8 in.
M20 x 1.51.5 mmPG 13.5 (20.4 mm)1/2 in.
M25 x 1.51.5 mmPG 16 (22.5 mm)3/4 in.
M32 x 1.51.5 mmPG 21 (28.3 mm)1 in.
M40 x 1.51.5 mmPG 29 (37.0 mm)1 1/4 in.
M50 x 1.51.5 mmPG 36 (47.0 mm)1 1/2 in.
M63 x 1.51.5 mmPG 48 (59.3 mm)2 in.
M75 x 1.51.5 mmNoneSee maker table
M90 x 1.5 or x 2 (varies by maker)2.0 mmNoneSee maker table

How to select a cable gland, step by step

Work through these steps for each line of the cable schedule. Most errors at site come from skipping step 2 or step 6.

What to put on the RFQ

A complete enquiry line lets the supplier match the gland without guessing.

  • Cable tag or schedule reference and quantity.
  • Cable type and armor: for example 4-core 35 mm² XLPE/SWA/PVC.
  • Inner and outer sheath diameters from the cable datasheet.
  • Area: zone, gas group and EPL; IECEx, ATEX or both.
  • Equipment protection: Ex d, Ex e, Ex nR or safe area.
  • Barrier or compression, if your specification decides it.
  • Entry thread: M20, M25 and so on, or NPT size.
  • Material and any plating requirement.
  • Accessories per gland and any deluge or IP68 requirement.
  1. Confirm the area: safe area, Zone 1 or Zone 2, gas group and any dust zone, from the hazardous-area drawing.
  2. Get the cable data: construction, inner sheath diameter, outer sheath diameter, armor type and armor wire size.
  3. Note the equipment protection concept: Ex d, Ex e, Ex nR, Ex i or non-Ex, and the entry thread size and type.
  4. Choose the gland type: unarmored or armored, single or inner and outer seal, compression or barrier per IEC 60079-14 and the project rule.
  5. Check certification: the gland approvals must cover the zone, gas group and equipment protection.
  6. Size the gland to both measured sheath diameters, not to the conductor size or a catalogue guess.
  7. Choose the material for the environment: brass, nickel-plated brass, 316 stainless or aluminum.
  8. Add accessories: shroud, earth tag, locknut, sealing washer, serrated washer, adaptor or stopping plug as needed.
  9. Check IP, deluge and temperature range against the location.
  10. Ask for certificate copies and installation instructions to go with the delivery.

Installation, inspection and common mistakes

Install every gland to the maker’s instructions, which form part of its certification. Torque values, seal choice and armor dressing differ between gland families.

IEC 60079-14 covers selection, installation and initial inspection of Ex installations. It requires the gland to match the cable diameter and does not allow tape or heat-shrink sleeving to build the cable up to fit.

Initial inspection checklist

  • Gland marking matches the certificate and the equipment protection concept.
  • Gland size suits the measured cable diameters; seals are fully compressed.
  • Armor sits fully in the clamp; earth tag is fitted and bonded where required.
  • Entry thread is fully engaged; sealing washer or O-ring is in place where the IP rating needs it.
  • Barrier compound has cured for the stated time before the circuit is energized.
  • Unused entries are closed with certified stopping plugs.
  • Shrouds are fitted outdoors and do not hide damage.

Common mistakes

  • Choosing the gland by conductor size instead of measured sheath diameter.
  • Using a non-Ex industrial gland on Ex equipment because the thread fits.
  • Fitting a compression gland where the project rule calls for a barrier.
  • Cutting the inner sheath short so the flameproof seal grips the cores or fillers.
  • Leaving out the entry sealing washer on an Ex e box, which drops its IP rating.
  • Mixing PG and metric parts, or forcing NPT into a metric entry.
  • Stacking adaptors beyond what the certificate allows.

Cable gland questions

What is the difference between Ex d and Ex e cable glands?

An Ex d gland is certified flameproof to IEC 60079-1. Its seal and entry thread must stop an internal explosion from escaping, so it can go into a flameproof enclosure. An Ex e gland follows IEC 60079-7 and keeps an increased-safety enclosure sealed to IP54 or better. Ex d glands can usually serve Ex e boxes, but Ex e glands cannot go into Ex d enclosures.

When do I need a barrier cable gland?

Use a barrier gland when IEC 60079-14 or your project rule requires one. This applies to direct entries into Ex d enclosures. Under the 2024 edition this depends on gas group, cable length and enclosure volume, with an Annex C cable test as an alternative route. Many owners simply require barrier glands on all Ex d direct entries.

How do I size a cable gland?

Measure or take from the datasheet the cable’s outer sheath diameter, and for armored cable the inner sheath diameter and armor wire size. Choose the gland size whose ranges cover all three. Do not size by conductor cross-section, and do not build up a small cable with tape or sleeving to fit a larger gland.

What does IP66/IP68 mean on a cable gland?

IP66 means the gland is dust-tight and resists powerful water jets. IP68 means it resists continuous immersion under conditions stated by the maker, such as a depth and time. The tests are separate, so a gland marked only IP66 is not proven for immersion. The IP rating at the enclosure usually also depends on the entry sealing washer.

What is a dual-certified cable gland?

It is one gland that holds more than one approval, for example Ex db and Ex eb. Many also hold Ex nR and dust Ex t. Plants use one gland family for flameproof, increased-safety and restricted-breathing equipment. Each approval must appear on the certificate for that exact gland type and size before you rely on it.

Which cable gland material is best for coastal plants?

Nickel-plated brass is the usual choice for outdoor units on the Gulf coast. Use 316 stainless steel for splash zones, jetties, offshore work and chemical vapor areas. Plain brass suits indoor rooms. Aluminum suits aluminum enclosures and AWA cable. Ask for the plating thickness when you specify nickel-plated brass.

Can I use a PG gland in a metric entry?

No. PG threads come from an older German system and have different diameters and pitches from metric ISO threads. A PG gland may start in a metric hole but will not seal or hold properly. Use a gland with the matching thread, or a certified adaptor where the equipment needs one.

What accessories go with a cable gland?

Common accessories are a PVC or LSF shroud, an earth tag to bond the armor and a locknut for clearance holes. Others are an entry thread sealing washer for IP, a serrated washer, adaptors, reducers and stopping plugs for unused entries. In hazardous areas, adaptors and stopping plugs must carry their own Ex certification.

Do cable glands have a temperature class?

Not normally. A cable gland carries a service temperature range for its body and seals. One maker’s armored gland is rated -60 °C to +130 °C. The temperature class comes from the equipment. Check that the gland range covers the entry temperature, which some equipment marks on its label.

What is the difference between SWA and braid glands?

SWA glands clamp round steel wires between a cone and a clamping ring, giving a strong earth path. Braid glands clamp a woven wire braid, usually with a grooved cone, and must bond it all round for screening. Many armored glands handle both by changing or reversing the clamping ring.

Does JTE hold IECEx or ATEX certificates for cable glands?

No. JTE supplies cable glands made by established manufacturers. Each Ex gland carries that manufacturer’s IECEx or ATEX certificate, and we pass on certificate copies and installation instructions with the order. JTE is an ISO 9001 certified supplier and can arrange third-party inspection on request.

Which standard covers non-hazardous-area cable glands?

IEC 62444 covers cable glands for electrical installations, and EN 62444:2013 replaced EN 50262 in Europe. It sets construction and performance tests for glands with IEC 60423 metric threads. Glands for mineral insulated cable are outside its scope. Hazardous-area glands must also meet the IEC 60079 series.

What is an Ex nR cable gland?

It is a gland approved for restricted-breathing enclosures under IEC 60079-15, used in Zone 2. The cable and gland together must keep the enclosure’s restricted-breathing seal, so the inner seal must be air-tight in both directions. Not every flameproof gland meets the Ex n requirements, so check the certificate.

What should a cable gland RFQ include?

Give the cable tag, cable type, armor type and both sheath diameters. Add the zone, gas group, equipment protection type, entry thread, material, accessories and quantity. Say whether barrier glands are required and whether IECEx, ATEX or both are needed. With that data a supplier can match each line without guessing.

Updated

Related

Hose clamps and cable ties

Stainless ties and clamps for cable tray and hose work.

Strut channel and fittings

Channel, brackets and clamps for cable and pipe supports.

Oil and gas

Fasteners and hardware for refineries and gas plants.

Send your cable schedule

Cable type, sheath diameters, zone and entry thread are enough for us to quote matching glands and accessories.